研究目的
To evaluate the hosting capacity of fast EV charging under voltage constraints in MV and LV distribution networks by considering the spatial distribution of fast EV charging points.
研究成果
The equalization factor of the spatial distribution is improved to approximately 70% using active and reactive power outputs from rooftop PV systems. The distribution line current, which increases as a result of the reactive power flow, is below the maximum allowable current limit. However, operational line current limits for reliable distribution network operations must be investigated for future widespread EV conditions.
研究不足
The study assumes ideal conditions for PV system distribution and does not fully account for operational line current limits for reliable distribution network operations under widespread EV conditions.