Cooperative Operation of R-SFCL and Online Current Limitation Strategy of GCPVS under Asymmetrical Faults
摘要: Grid-connected photovoltaic (GCPVS) should remain grid-connected and inject specified reactive current in accordance with fault-ride-through (FRT) requirements. To minimize voltage ripples on the DC link voltage and restrict the maximum phase currents, a modified online current limitation strategy (OCLS) is presented in this paper. Transient performance of GCPVS is enhanced as resistive-type superconducting fault current limiter (R-SFCL) is applied under severe asymmetrical faults. By introducing proper resistance selection process, the cooperative operation of OCLS and SFCL is proved to be effective.
关键词: reactive power control,transient performance,superconducting fault current limiters (FCL),online current limitation strategy (OCLS),photovoltaic systems,Fault ride-through (FRT) capability,symmetrical and asymmetrical faults