研究目的
To study the harmonic impact of a significantly large photovoltaic (PV) solar farm of 20 MW in a utility distribution system.
研究成果
It is concluded that this large solar farm may not cause any substantial voltage distortion on the distribution network during steady-state operating conditions. However, recommendations are made for utilities to perform such studies to ensure the safe operation of critical loads.
研究不足
The impacts of ambient harmonics and harmonics generated during transient situations (capacitor switching etc.) have not been considered in this simulation study.
1:Experimental Design and Method Selection:
The utility network is modeled in detail using the commercial grade PSCAD/EMTDC software, validated through load flow studies conducted by CYME software and correlated with SCADA measurements.
2:Sample Selection and Data Sources:
Harmonics data instrumented for several months were provided by the transmission utility at the two solar farm units and at the main feeder substation.
3:List of Experimental Equipment and Materials:
PSCAD/EMTDC software, CYME software, SCADA measurements.
4:Experimental Procedures and Operational Workflow:
The validated network model is used for network resonance study and harmonics impact analysis of the solar farms under different network conditions.
5:Data Analysis Methods:
The harmonics data were utilized for extensive harmonic impact studies with widely different short-circuit levels and network resonance conditions.