研究目的
To determine the variation in power flow parameters of the PV integrated distribution system.
研究成果
The integration of solar PV affects the operation of existing distribution network such as reverse power flow occurs in the lines and voltage rise takes place at the load end, which is adjusted and maintained within the limits by the line voltage regulators. Before penetrating the solar PV in the conventional distribution system, an exhaustive study of variation in power flow parameters is required in order to ensure the good quality and reliability of supply to the consumers.
研究不足
The study focuses on a specific model of Indian urban distribution feeder and may not be directly applicable to other systems without adjustments.
1:Experimental Design and Method Selection:
A reformulated 3-phase Newton-Raphson (N-R) power flow algorithm based on current injection method is used for the solar PV integrated unbalance distribution system.
2:Sample Selection and Data Sources:
An 11/
3:433 kV realistic rural distribution feeder of Indian utility is modeled. List of Experimental Equipment and Materials:
Solar PVs are installed at the distribution networks.
4:Experimental Procedures and Operational Workflow:
The operational characteristics of distribution feeder are analyzed with and without solar PV integration.
5:Data Analysis Methods:
The results show changes in branch current loading, neutral current, power losses and power flow direction after solar PV integration.