研究目的
Investigating the optical characterization of inhibitor content in transformer oil by utilizing the ultraviolet-visible (UV-Vis) spectroscopy technique to potentially develop a portable and low cost optical sensing device for detection.
研究成果
Inhibitor content in transformer oil can be characterized optically in the UV-Vis region as multiple peak absorption can be observed. The difference in peak absorbance near 450 nm suggests the difference in inhibitor content concentration in transformer oil. The results demonstrate the potential of detecting inhibitor content in transformer oil at very low cost by utilizing Silicon photodetector for the UV-Vis optical sensing system.
研究不足
Further work with more controlled oil samples are needed to fully establish a clear relationship between the peak absorbance at 450 nm and the inhibitor content concentration of transformer oil.